Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency Telephone shall have Battery Back up. 8/22/2022
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Yes No A Class ABC Fire Extinguisher shall be provided in Elevator Machine Rooms. 8/22/2022
A17.1-2016 : Elevators 3.9 - Floor and emergency identification numbering 2.29.2 Yes No Hoistway Doors shall have floor numbers not less than (4 in) in height on the Hoistway side of the enclosure or doors. 8/22/2022
A17.1-2016 : Elevators 4.5 - Access to Hoistway 2.12.7 Yes No Per A17.1 2016 Item 2.12.7.3.3(3) Pit Entry level Access switch shall enable the car to move in the up direction to a point between (84 in) and (96 in) from the floor level to the bottom of the platform guard. 8/22/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.26.2.7 Yes No Emergency Stop Switch in Pit shall when on the Stop position shall cause the electric power to be removed from the elevator driving machine motor. 8/22/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.1 Phase I Emergency Recall Operation Yes Yes A17.1 Item 2.27.3.3.1(i) Means to prevent the operation of the floor selection means or door operating buttons shall be rendered inoperative. 8/22/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection) Yes No Per A17.1 2016 Item Car Stop Switch if provided shall not be overridden on Phase I Recall. 8/22/2022