A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection)
|
x
|
|
Per A17.1 2016 Item Car Stop Switch if provided shall not be overridden on Phase I Recall.
|
8/22/2022
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency Telephone shall have Battery Back up.
|
8/22/2022
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
A Class ABC Fire Extinguisher shall be provided in Elevator Machine Rooms.
|
8/22/2022
|
A17.1-2016 : Elevators
|
3.9 - Floor and emergency identification numbering
|
2.29.2
|
x
|
|
Hoistway Doors shall have floor numbers not less than (4 in) in height on the Hoistway side of the enclosure or doors.
|
8/22/2022
|
A17.1-2016 : Elevators
|
4.5 - Access to Hoistway
|
2.12.7
|
x
|
|
Per A17.1 2016 Item 2.12.7.3.3(3) Pit Entry level Access switch shall enable the car to move in the up direction to a point between (84 in) and (96 in) from the floor level to the bottom of the platform guard.
|
8/22/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.26.2.7
|
x
|
|
Emergency Stop Switch in Pit shall when on the Stop position shall cause the electric power to be removed from the elevator driving machine motor.
|
8/22/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.1 Phase I Emergency Recall Operation
|
x
|
x
|
A17.1 Item 2.27.3.3.1(i) Means to prevent the operation of the floor selection means or door operating buttons shall be rendered inoperative.
|
8/22/2022
|