Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 4.5 - Access to Hoistway 2.12.7 x Per A17.1 2016 Item 2.12.7.3.3(3) Pit Entry level Access switch shall enable the car to move in the up direction to a point between (84 in) and (96 in) from the floor level to the bottom of the platform guard. 8/22/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.26.2.7 x Emergency Stop Switch in Pit shall when on the Stop position shall cause the electric power to be removed from the elevator driving machine motor. 8/22/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency Telephone shall have Battery Back up. 8/22/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.1 Phase I Emergency Recall Operation x x A17.1 Item 2.27.3.3.1(i) Means to prevent the operation of the floor selection means or door operating buttons shall be rendered inoperative. 8/22/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection) x Per A17.1 2016 Item Car Stop Switch if provided shall not be overridden on Phase I Recall. 8/22/2022
A17.1-2016 : Elevators 3.9 - Floor and emergency identification numbering 2.29.2 x Hoistway Doors shall have floor numbers not less than (4 in) in height on the Hoistway side of the enclosure or doors. 8/22/2022
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x A Class ABC Fire Extinguisher shall be provided in Elevator Machine Rooms. 8/22/2022