Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 No No In case of fire don't use elevator signage needed 7/29/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) Yes No Elevator Emergency Power could not be tested for lack of the Dry Contacts Required for the delay of Building Power Transfer to the Generator Power. Must Reinspect. 8/11/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability No No missing communication loss signal device
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No missing fire ext on top floor near elev controls
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 No No flex conduit in overhead longer than 6 foot. pipe same or shorten same
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No display current elev certificate top floor by elev control or in car