Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability missing communication loss signal device
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 flex conduit in overhead longer than 6 foot. pipe same or shorten same
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate display current elev certificate top floor by elev control or in car
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 missing fire ext on top floor near elev controls
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x Elevator Emergency Power could not be tested for lack of the Dry Contacts Required for the delay of Building Power Transfer to the Generator Power. Must Reinspect. 8/11/2021
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 In case of fire don't use elevator signage needed 7/29/2022