Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 x If sprinklers are going to be installed in the machine space, a shunt trip disconnect is required. 12/6/2021
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Provide current operating state permit 1/11/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x Remove the emergency power switch from panel and cover. Building is not equipped with an emergency generator that powers the elevator. 12/6/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 12/6/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits x The pit shall be cleaned out. 12/6/2021