A17.1-2016 : Elevators
|
4.8 - Hoistway enclosure
|
2.1.1
|
x
|
|
Seal around greenfield going through hoistway wall. Remove wood in hoistway
|
5/11/2022
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.10.2.2.1(o)
|
x
|
|
Braille car designation at LL, P1, 6 floor
|
5/11/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3
|
x
|
x
|
FAID devices need to be tested
|
5/11/2022
|
A17.1-2016 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
x
|
|
Hoistway ventilation damper inoperative
|
5/11/2022
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone inoperative. Re-inspection required
|
5/11/2022
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Video camera was working on operator end. They could not send a message on the video screen, voice communicator was working. Re-inspection required
|
|