A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(f)
|
x
|
|
Increase control space illumination to 19ft candles measured at the floor in front of the controller
|
8/20/2021
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.10.2.2.2(l)
|
x
|
|
Install a fire extinguisher near the control space on the top floor
|
8/20/2021
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.10.2.2.5(a)
|
x
|
|
Increase pit illumination to 10ft candles though out measured at the pit floor
|
8/20/2021
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
A monthly record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. The log is on site, but monthly testing has not been recorded.
|
2/21/2023
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
2/21/2023
|