Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.12 - Car enclosure 2.14.1.9 x car floor covering has not been installed, trip hazard at the sills 8/2/2023
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x the light for the top landing shall not be on a motion switch, the elevator control space is in the top landing jamb 8/2/2023
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 x turn on the air conditioning on the top floor to keep elevator controller at the manufactures recommended temperature range and humidity 8/2/2023