Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone shall be made operable. Re-inspection required 2/23/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) x Pit light shall be 10 fc minimum 2/23/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Only 2 way communication working on 3 way system, needs repaired. Re-inspection required 4/24/2023
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 Test heat detector activation of shunt trip
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 x Heat detector shall be installed not more than 24" from sprinkler head 2/23/2023