Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 8/30/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate Post code data p[late conforming to sec 8.9 on controller 8/3/2021
MO Minimum : Elevators (A) - Hoistways (A)1 sight guard needs to be re-secured at 3rd landing 11/25/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Machine Room Fire Extinguisher shall have current monthly/annual test tag 11/25/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. 11/25/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Alarm shall work with power loss. (REINSPECTION within 30 days) 10/30/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Five year full load test needed. Last full load test performed 11/2010 8/5/2020
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Additional lighting is needed in machine room
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Light in pit is not working