A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
x
|
|
A17.1, Section 2.8.3.4 (a) With sprinklers in Elevator pits all electrical equipment less than 48 inches from pit floor shall be Weather Proof (Type 4 as specified in NEMA 250)
|
3/31/2023
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4
|
x
|
|
A17.1 Section 2.2.4.1 Pit Ladder shall not extend less than 48 inches above sill of the access door.
|
3/31/2023
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
In Elevators provided with Firefighters Emergency Operation a drain or sump pump shall be provided. The sump pump/drain shall have the capacity to remove a minimum of (3ooo gal/h)per elevator. l
|
3/31/2023
|
A17.1-2016 : Elevators
|
6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators
|
2.27.3
|
x
|
x
|
Firefighters Emergency Service Operation could not be verified, all of the Smoke Alarms, Heats & Shunt Trip devices had not been programmed.
|
3/31/2023
|