Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 x A17.1 Section 2.2.4.1 Pit Ladder shall not extend less than 48 inches above sill of the access door. 3/31/2023
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 x A17.1, Section 2.8.3.4 (a) With sprinklers in Elevator pits all electrical equipment less than 48 inches from pit floor shall be Weather Proof (Type 4 as specified in NEMA 250) 3/31/2023
A17.1-2016 : Elevators 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators 2.27.3 x x Firefighters Emergency Service Operation could not be verified, all of the Smoke Alarms, Heats & Shunt Trip devices had not been programmed. 3/31/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x In Elevators provided with Firefighters Emergency Operation a drain or sump pump shall be provided. The sump pump/drain shall have the capacity to remove a minimum of (3ooo gal/h)per elevator. l 3/31/2023