Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone Monitoring device not operating 1/21/2022
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 x Close all machine room penetrations to maintain fire rating. 1/21/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Close all hoistway penetrations to maintain the fire rating 1/21/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Hoistway has drywall screws protruding into the hoistway. Remove all sharp hoistway protrusions. 1/21/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x Pit sump shall be covered even with the pit floor 1/21/2022