A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Close all hoistway penetrations to maintain the fire rating
|
1/21/2022
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.7.1
|
x
|
|
Close all machine room penetrations to maintain fire rating.
|
1/21/2022
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work on 110v power. The answering service was unable to provide location of the unit.
|
12/4/2025
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work on auxiliary power. Unable to obtain dial tone.
|
12/4/2025
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Hoistway has drywall screws protruding into the hoistway. Remove all sharp hoistway protrusions.
|
1/21/2022
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone Monitoring device not operating
|
1/21/2022
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.6 Sump Pump Covers
|
x
|
|
Pit sump shall be covered even with the pit floor
|
1/21/2022
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
This disconnect was tripped upon arrival. The mechanic closed the switch. The unit powered on, but could not get it up and running. The only things tested were emergency light, bell, and phone. The entire annual inspection still needs to be completed.
|
12/4/2025
|