Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Yes No A pit ladder shall be provided meeting the requirements of A17.1 2016 - 2.2.4. 4/20/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device Yes Yes When sprinklers are installed in elevator pits, automatic fire detection shall be installed to initiate elevator recall in accordance with 2.27.3.2.1( c) of A17.1 2016, A17.2 item 6, CSR 40-5.065(S)1 , NFPA 72 2013 21 .3.3, 21 .3.7, 21 .3.8, 21 .4, 21 .5 Note: A water-flow switch shall be permitted to initiate elevator recall upon activation of a sprinkler installed at the bottom of the elevator hoist-way (the elevator pit), provided the waterflow switch and pit sprinkler are installed on a separately valved sprinkler line dedicated solely for protecting the elevator pit, and the water-flow switch is provided without time-delay capability. 4/20/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 Yes No Feeder locations for the lighting branch circuit shall be marked near the disconnect in the means necessary for tests. 4/20/2022
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.10.2.2.2(l) Yes No An ABC fire extinguisher with a current test tag shall be mounted convenient to the means necessary for test at the top landing. 4/20/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation Yes No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 4/20/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4 Instructions for Locating Maintenance Records Yes No Instructions for locating maintenance records for viewing on-site shall be posted at the means necessary for test and shall be permanently legible with characters a minimum of 3mm in height. 4/20/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test Yes No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Currently schematics, layout drawings, unique procedures booklet, and door operator guide are present. Provide the complete MCP approved by MO AHJ. 7/17/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test Yes No Instructions for locating maintenance records for viewing on-site shall be posted at the means necessary for test and shall be permanently legible with characters a minimum of 3mm in height. 7/17/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No 2-way communication device shall give proper location message. 2/16/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4 Instructions for Locating Maintenance Records No No Instructions for locating maintenance records for viewing on-site shall be posted at the means necessary for test and shall be permanently legible with characters a minimum of 3mm in height. 2/16/2024
A17.1-2016 : Elevators 3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.6.4.19.17 Earthquake Operation Yes No Counterweight "ring and string" earthquake detection shall work. 2/16/2024