A17.1-2016 : Elevators
|
11.7 - Disconnecting Means
|
2.7.3.5
|
x
|
|
Location of power feed not marked on disconnects
|
3/11/2022
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.10.2.2.2(r)
|
x
|
|
Disconnects for the main line and cab lighting not properly fused. Fuses rated too high for circuit it is protecting
|
3/11/2022
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Increase Control Space illumination to 10 Ft candles minimum
|
3/11/2022
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Increase Machine Space illumination to 19ft candles minimum
|
3/11/2022
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Seal hoistway penetrations around conduit above top floor door
|
3/11/2022
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Remove cardboard from around hoistway doors
|
3/11/2022
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Remove screws protruding from top of hoistway
|
3/11/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Increase pit illumination to 10 ft candles throughout. Measured at the pit floor
|
3/11/2022
|