Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Seal hoistway penetrations around conduit above top floor door 3/11/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Remove cardboard from around hoistway doors 3/11/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Remove screws protruding from top of hoistway 3/11/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Increase pit illumination to 10 ft candles throughout. Measured at the pit floor 3/11/2022
A17.1-2016 : Elevators 11.7 - Disconnecting Means 2.7.3.5 x Location of power feed not marked on disconnects 3/11/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Increase Control Space illumination to 10 Ft candles minimum 3/11/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Increase Machine Space illumination to 19ft candles minimum 3/11/2022