A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Remove standing water from elevator pit. Sump pump does not appear to be working
|
10/15/2024
|
|
A17.1-2016 : Elevators
|
1.7 - Car door or gate
|
8.6.4.13.1 Door Systems General
|
|
|
Elevator rear car door has a 3/4 inch gap at the bottom when closed. Adjust door to a maximum of 3/8 of a inch gap.
|
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
10/15/2024
|