Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 4.8 - Hoistway enclosure 2.1.1 Yes No Complete fire caulking in hoistway, and around landing doors. 12/1/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.4 Yes No Provide a single, non GFCI outlet in pit for sump pump. 12/1/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 Yes No Provide heat detectors in elevator lobby at the floor the controller is located. 2.8.3.3.2 12/1/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Yes No Provide an MCP for elevator. 12/1/2022