A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
x
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures, fire service check charts, and maintenance log are missing.
|
2/22/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
The overhead shall have a firemans' return initiating device.
|
2/22/2022
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
8.7.2.1.1 Hoistway Enclosure Walls
|
x
|
|
The integrity of the rear hoistway wall shall be determined.
|
2/22/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
x
|
|
The pit shall be cleaned.
|
2/22/2022
|
A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
8.10.2.2.3(s)
|
x
|
|
Ledges in the hoistway and overhead shall be properly beveled.
|
2/22/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Re-inspection required
|
3/4/2025
|