Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation x A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures, fire service check charts, and maintenance log are missing. 2/22/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. Re-inspection required 3/4/2025
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 8.10.2.2.3(s) x Ledges in the hoistway and overhead shall be properly beveled. 2/22/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1 Hoistway Enclosure Walls x The integrity of the rear hoistway wall shall be determined. 2/22/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x The overhead shall have a firemans' return initiating device. 2/22/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits x The pit shall be cleaned. 2/22/2022