Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.1 Phase I Emergency Recall Operation x x When sprinklers are installed in elevator pits, automatic fire detection shall be installed to initiate elevator recall in accordance with 2.27.3.2.1 of A17.1 2016. Note: A water-flow switch shall be permitted to initiate elevator recall upon activation of a sprinkler installed on a separately valved sprinkler line dedicated solely for protecting the elevator pit, and the water-flow switch is provided without time-delay capability. 11/9/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation x A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. 11/9/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 x Heat-sensing fire detectors shall be located on the ceiling not less than 4 inches from the sidewall or on the sidewalls between 4 inches and 12 inches from the ceiling. Note: The heat detector in the pit do not meet these requirements. 11/9/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 x The electrical equipment in the pit located less than 48" above the floor (except earthquake protective devices) shall be weatherproof, and the wiring (except traveling cables) shall be identified for use in wet locations. Note: The heat detector in the pit doesn't meet these requirements. 11/9/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(c)(1) x A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. The written record shall be kept in the machine room. 11/9/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(d)(1) x Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 11/9/2022
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to disconnected from its load when the disconnecting means is in the open position. Note: The main power shunt trip device shall be equipped with the required auxiliary contact as required and connected to the elevator control. 11/9/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.3(h) Two-way communications shall not go to an automated answering system. x The two-way communication means (in car telephone) shall provide on demand to authorized personnel, information that identifies the building location and elevator number and that assistance is required. 11/9/2022
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.11.11.1 x The flooring on the top landing shall be installed. Note: A tripping hazard presently exists at the top landing because the floor in front of the elevator isn't complete. 11/9/2022