Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.20 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.11.2.1.1(y) No No "Earthquake Mode" visual indicator(jewel) in COP shall work, provide cover if not installed, or apply for variance to remove. Unit does not have EQ detection equipment in pit, HW, or MR. No counterweight derailment installed
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No : Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.5 Wedge Rope Sockets No No 2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced. 9/12/2024
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No 4 x 4 electrical box in machine room needs to have wiring inside box and cover installed. 9/12/2024
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No 4 x 4 electrical box in machine room needs to have wiring inside box and cover installed.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation No No A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP is present. Needs all the documentation for 2022 & 2023. 9/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors). 9/12/2024
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 Yes No Counterweight runby does not meet Code Minimum of 6".
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Yes No Emergency communication loss monitor shall work. 2/22/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.19.15 Emergency Communications Yes No Emergency communications loss monitor shall work, activate visual and audible signals indicating the loss of the communication signal.
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) Yes No Emergency lighting shall work. 2/22/2024
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 2.18.6 Yes No Governor - Remote SET/RESET functions shall work as designed.
A17.1-2016 : Elevators 4.2 - Hoistway doors 2.11 Yes No Hoistway door safety retainers/fire tabs shall be installed at the bottom of all hoistway doors. Multiple doors missing retainers.
A17.1-2016 : Elevators 4.2 - Hoistway doors 2.11 Yes No Hoistway door safety retainers/fire tabs shall be installed at the bottom of all hoistway doors. Multiple doors missing retainers. 2/22/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No MCP - Fire Service must be tested and properly documented monthly on Log Shee
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No MCP, including PM records. No MCP/Records for 2022, 2023, 2024, 2025, 2026 found.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall work. The voice works but video/text does not. 2/22/2024