A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
No
|
No
|
MCP - Fire Service must be tested and properly documented monthly on Log Sheet
|
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
No
|
No
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. The logs are mostly blank. Need all documentation from 2022 & 2023.
|
6/10/2025
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
Yes
|
No
|
Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
|
|
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
2.7.6.3.4
|
Yes
|
No
|
Remote governor set/rest does not work. Take corrective action as needed.
|
2/22/2024
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
Yes
|
No
|
Emergency communications loss monitor shall work.
|
2/22/2024
|
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.7.2 Seizing of Rope Ends
|
No
|
No
|
2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. They are currently wrapped in electrical tape.
|
6/10/2025
|