Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x All Phase I Recall Devices Shall Be Tested 6/30/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Close all hoistway penetrations 6/30/2022
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 x Close Control space penetrations 6/30/2022
A17.1-2016 : Elevators 2.4 - Machine space 2.7.3 x Control space door shall be self-closing, self-locking 6/30/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x Cover pit sump even with pit floor 6/30/2022
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 2.1.4 x If determined by the local building codes hoistway vent is not required. remove wood blocking and replace with 2hr rated closure 6/30/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Increase Control space to 19 footcandles minimum 6/30/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Increase Machine space illumination to 19 footcandles minimum 6/30/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Increase pit illumination to 10 footcandles minimum 6/30/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Install smoke detector in the Control space 6/30/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The video/text emergency communication means shall conform to A17.1 - 2019, Section 2.27. The text operation is not working. See MO Memorandum 013. A variance shall also be applied for.