A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
|
|
Install missing wire way covers in control room over top of controller, adjust traveling cable in wire way, and install missing cover on 90' wireway fitting at top of hoistway in machine space.
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The video/text emergency communication means shall conform to A17.1 - 2019, Section 2.27. The video and text operation is not working. See MO Memorandum 013. A variance shall also be applied for.
|
|