Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide phone line for 3-way communication device and test 8/1/2022
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 x Seal all machine room penetrations 8/1/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Label all disconnects in the machine room with feed source location 8/1/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Provide a means to prevent the HVAC condensate from contacting the disconnects and controller 8/1/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Seal all hoistway penetrations 8/1/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Three way visual communication was unable to be tested due to no training on the system. Proper training required and then shall be reinspected 11/27/2023