A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
x
|
|
A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. – 8.6.1.4 or 8.6.10.1
|
9/13/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(1)
|
x
|
|
A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. The written record shall be kept in the machine room.
|
9/13/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(d)(2)
|
x
|
|
Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
|
9/13/2022
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
Feeder locations for the main and lighting branch circuits shall be marked on the disconnects.
|
9/13/2022
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.10.2
|
x
|
|
Illumination at Landing Sills. The building corridors shall be so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 10 foot candles. There is no permanent lighting at the bottom landing.
|
9/13/2022
|