Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.1 Phase I Emergency Recall Operation x x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: phase I fireman recall operation will not operate due to a malfunctioning smoke detector/fire alarm panel. Repair and reinspection is required. 8/5/2025