Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Mainline and lighting disconnects need feeder location labeling. 1/30/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Orange spray foam "Fire Block" not allowed. Product is not compliant with IBC or NFPA 72 as 1.5hr fire rated fire penetration sealant for commercial applications. Hoistway penetration sealant must be a compliant fire resistive sealant product. Replace/recover with compliant product. Non-compliance statement can be found on the back of the cans of the existing orange sealant. 1/30/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Yellow spray foam insulation not allowed. Product is not compliant with IBC or NFPA 72 as a 1.5hr fire rated fire penetration sealant for commercial applications. Hoistway wall covering must be a compliant fire restrictive product. Replace/recover with compliant product or provide compliance rating documentation for current sealant. Contractor indicated they may apply DC315 Coating at a minimum wet film thickness of 24mil wet (based on ICC ESR-3500 for Proseal LE) will create the thermal barrier needed and maintain the integrity of the insulation in the event of a hoistway fire. 1/30/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x There is exposed wood, without fire-rated coating, throughout the hoistway, under sill, etc. 1/30/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Provided pit sump pump documentation to ensure proper capacity (3000 GPH per elevator at 14' of head) and the presence of automatic float operation (no float switch seen at this time). 1/30/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.1 Phase I Emergency Recall Operation x x Lobby fire status panel display damaged. Repair and fully test. 1/30/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x FAID failed to initiate elevator recall. Test all devices. 1/30/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine space lighting shall be not less than 19fc with cartop level on top floor, as measured from the cartop. 1/30/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Lighting at controller access floor (10th floor) shall not be less than 19fc, measured at the floor level. 1/30/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Secure metallic wiring properly in top of hoistway. 1/30/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Top of hoistway lighting switch must be accessible & visible from both landings. 1/30/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x GFI located in top of hoistway shall work. 1/30/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Cast iron piping and HVAC ducts are not part of the elevator system or subsystems. These shall be removed or properly covered. 1/30/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Fire suppression/sprinkler systems in elevator lobbies not fully installed at this time. Verification of completed installation required. 1/30/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x 10th floor fire extinguisher shall be ABC rated, not just BC rated. 1/30/2025