Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.3 - Operating control devices 8.10.3.2.1(c) x The main egress star on the COP and the numbers on the door jamb shall be at the 2nd floor. 5/31/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x All hall fixtures shall be properly installed and flush with the mounting surface. 5/31/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation x A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 5/31/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(d)(1) Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1(b) x Seal the ceiling joint and edges at the top of the hoistway. 5/31/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1(b) x Remove any wood and properly grout the hoistway door frames and all gaps and penetrations in the hoistway walls. 5/31/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1(b) x Fire caulk all penetrations including, but not limited to, the sprinkler pipe, the sump discharge line and electrical conduit. 5/31/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Provide documentation of the sump pump capacity. 5/31/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) x The fire service visual indicator in the hall shall work. 5/31/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site.
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.