Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable. Re-inspection required 10/23/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 x Finish control space lighting, 19 ft candles minimum. Re-inspection required 6/16/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Sump pump runs constantly, needs to be repaired. Re-inspection required 6/16/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.10.2.2.5(a) x All pit receptacles required to be GFI. Re-inspection required NFPA 70 Section 620 6/16/2022