Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Increase control space illumination to 19 ft candles minimum on 2nd floor. Re-inspection required 7/6/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.3 x Oilminder needs to be removed from pit, so alarm can be shut off. Pit shall be accessible to elevator personnel only. Re-inspection required 7/6/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 x Install heat detection in control space 24 inches maximum from sprinkler on 2nd floor in front of elevator. Re-inspection required 7/6/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Install a smoke detector in the elevator machine space in pit. Re-inspection required 7/6/2022