Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.3 Yes No Oilminder needs to be removed from pit, so alarm can be shut off. Pit shall be accessible to elevator personnel only. Re-inspection required 7/6/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device Yes Yes Install a smoke detector in the elevator machine space in pit. Re-inspection required 7/6/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 Yes No Increase control space illumination to 19 ft candles minimum on 2nd floor. Re-inspection required 7/6/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 Yes No Install heat detection in control space 24 inches maximum from sprinkler on 2nd floor in front of elevator. Re-inspection required 7/6/2022