A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.3
|
x
|
|
Oilminder needs to be removed from pit, so alarm can be shut off. Pit shall be accessible to elevator personnel only. Re-inspection required
|
7/6/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Install a smoke detector in the elevator machine space in pit. Re-inspection required
|
7/6/2022
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Increase control space illumination to 19 ft candles minimum on 2nd floor. Re-inspection required
|
7/6/2022
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
x
|
|
Install heat detection in control space 24 inches maximum from sprinkler on 2nd floor in front of elevator. Re-inspection required
|
7/6/2022
|