A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
All fire alarm initiating devices and phases of fire service shall be tested.
|
1/26/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.10.2.2.1(q)
|
x
|
|
An emergency generator is being installed. Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
1/26/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal)
|
|
|
Elevator tested on standby emergency generator power it passed, but the emergency power bezel in the lobby went out while the elevators werwe running on emergency power. Light has to remain on until normal power is restored. Reinspection maximum 30 days
|
6/26/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency power must be tested.
|
3/11/2025
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
Maintenance record have no entries.
|
3/19/2025
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.4.19.3
|
x
|
|
Make repairs to elevator so testing can be completed.
|
3/11/2025
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Patch all holes and penetrations in the hoistway.
|
1/26/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post certificate in machine room.
|
3/19/2025
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
1/26/2023
|