Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x All fire alarm initiating devices and phases of fire service shall be tested. 1/26/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.10.2.2.1(q) x An emergency generator is being installed. Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 1/26/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Elevator tested on standby emergency generator power it passed, but the emergency power bezel in the lobby went out while the elevators werwe running on emergency power. Light has to remain on until normal power is restored. Reinspection maximum 30 days 6/26/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency power must be tested. 3/11/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) Maintenance record have no entries. 3/19/2025
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.19.3 x Make repairs to elevator so testing can be completed. 3/11/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Patch all holes and penetrations in the hoistway. 1/26/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post certificate in machine room. 3/19/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 1/26/2023