Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Elevator tested on standby emergency generator power it passed, but the emergency power bezel in the lobby went out while the elevators werwe running on emergency power. Light has to remain on until normal power is restored. Reinspection maximum 30 days 6/26/2024
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 x Lights inside the car must be properly secured to the canopy. 1/26/2023