Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | x | Lights inside the car must be properly secured to the canopy. | 1/26/2023 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | Elevator tested on standby emergency generator power it passed, but the emergency power bezel in the lobby went out while the elevators werwe running on emergency power. Light has to remain on until normal power is restored. Reinspection maximum 30 days | 6/26/2024 | ||
A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Lighting at top floor where controller is located must be at least 19 foot-candles. | 1/26/2023 |