Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency communications/phone in car not working reinspection 30 day maximum 3/21/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x The generator currently runs elevator but does not give signal to elevator by lighting the jewel in the lobby. The emergency power indicator jewel in the lobby shall illuminate when elevator is operating on the emergency generator. 3/1/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Must complete emergency power test. 3/11/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.7.2.27.4 x Stand by power illuminated bezel in elevator lobby not working. State has granted 120 day extension. 3/21/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Elevator tested on standby emergency generator power it passed, but the emergency power bezel in the lobby went out while the elevators werwe running on emergency power. Light has to remain on until normal power is restored. Reinspection maximum 30 days. 7/11/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post certificate in machine room