Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 No No 2.8.3.3.2 Device when activated shall remove the power to the disconnect prior to the application of water 2/5/2024
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Yes No Access and working space shall be provided and maintained about all electrical equipment to permit ready & safe operation and maintenance of such equipment 10/4/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 No No Disconnects per NFPA shall have 36in front and 30in side clear and unobstructed. Close hole in floor in front of the discinnect 2/5/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 No No Electrical wiring shall meet NFPA 70 Disconnects shall have sorce location labeled on them 2/5/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone calls out cannot make audio or visual contact. 12/18/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 Yes No Heat detector shall be installed not more than 24" from sprinkler head. Re-inspection required 10/4/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 Yes No Lighting in front of the controller, panel shall be of at least 19 fc and the pit shall have at least 10 fc at farthest point of light. Re-inspection required 10/4/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Yes No Pit illumination to be 10fc minimum 10/15/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.3 Yes No Sump pump needs to be wired for proper operation. Re-inspection required 10/4/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27.1 Phase I Emergency Recall Operation After Device Actuation Yes Yes Test all recall devices 10/15/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No No recall device tested, no one there to perform test. Video monitoring needs to be tested, no internet. Re-inspection required 10/4/2022