A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
|
|
2.8.3.3.2 Device when activated shall remove the power to the disconnect prior to the application of water
|
2/5/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
|
|
Electrical wiring shall meet NFPA 70 Disconnects shall have sorce location labeled on them
|
2/5/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
|
|
Disconnects per NFPA shall have 36in front and 30in side clear and unobstructed. Close hole in floor in front of the discinnect
|
2/5/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone calls out cannot make audio or visual contact.
|
12/18/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
x
|
|
Heat detector shall be installed not more than 24" from sprinkler head. Re-inspection required
|
10/4/2022
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Lighting in front of the controller, panel shall be of at least 19 fc and the pit shall have at least 10 fc at farthest point of light. Re-inspection required
|
10/4/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.3
|
x
|
|
Sump pump needs to be wired for proper operation. Re-inspection required
|
10/4/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
No recall device tested, no one there to perform test. Video monitoring needs to be tested, no internet. Re-inspection required
|
10/4/2022
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
x
|
|
Access and working space shall be provided and maintained about all electrical equipment to permit ready & safe operation and maintenance of such equipment
|
10/4/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Pit illumination to be 10fc minimum
|
10/15/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
3.27.1 Phase I Emergency Recall Operation After Device Actuation
|
x
|
x
|
Test all recall devices
|
10/15/2022
|