A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair inoperative emergency phone
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
|
|
Repair inoperative communication failure detection
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Lighting in front of the controller, panel shall be of at least 19 fc
|
10/4/2022
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
|
|
2.8.3.3.2 Device when activated shall remove the power to the disconnect prior to the application of water
|
2/5/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
|
|
Electrical wiring shall meet NFPA 70. Disconnects shall have the sorce location labeled on them.
|
2/5/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
x
|
|
Heat detector shall be installed not more than 24" from sprinkler head
|
10/4/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
3.27.1 Phase I Emergency Recall Operation After Device Actuation
|
x
|
x
|
Test all recall devices
|
10/15/2022
|