Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 2.8.3.3.2 Device when activated shall remove the power to the disconnect prior to the application of water 2/5/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 Electrical wiring shall meet NFPA 70. Disconnects shall have the sorce location labeled on them. 2/5/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 x Heat detector shall be installed not more than 24" from sprinkler head 10/4/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Lighting in front of the controller, panel shall be of at least 19 fc 10/4/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Repair inoperative communication failure detection
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) x Repair inoperative emergency phone