Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 2.17.7 x x 2.17.7.3 - This unit has been red-tagged and taken out of service by Kone Elevator. It shall remain out of service until repairs can be made, and a re-inspection performed and witnessed. The car safety mechanism switch shall operate before or at the time of application of the safety. 11/15/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x The emergency/standby power shall be tested. (2nd Notice) 7/15/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x The emergency/standby power shall be tested. 6/26/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x The emergency/standby power shall be tested. Note: Building personnel were not prepared to test this during inspection. 11/15/2023