Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x A means to display video to observe passengers at any location on the car floor, to authorized personnel for entrapment assessment, shall be provided. The phone works in every way (text, audio, indicators, etc.) except the video is not working. 6/26/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x The emergency/standby power shall be tested. Note: Building personnel were not prepared to test this during the inspection. 6/26/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x The emergency/standby power shall be tested. (2nd Notice) 7/15/2024