Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.3 | x | 2.8.3.3.2 - Pump unit is in the pit. Pit is sprinkled but no heat detector, which shall initiate shunt trip for unit power. Install heat detector and test shunt. | 11/9/2023 |