Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 x 2.8.3.3.2 - Pump unit is in the pit. Pit is sprinkled but no heat detector, which shall initiate shunt trip for unit power. Install heat detector and test shunt. 11/9/2023