Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 Yes No 2.8.3.3.2 - Pump unit is in the pit. Pit is sprinkled but no heat detector, which shall initiate shunt trip for unit power. Install heat detector and test shunt. 11/9/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current operating certificate shall be posted in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher is out of date.