Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. The voice works, but video/text does not. 2/22/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. 6/11/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation A code compliant MCP and all the on-site documentation required shall be provided in the machine room. All logs are blank. Need all documentation from 2022 & 2023. 6/11/2025
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.7.2 Seizing of Rope Ends 2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. They are currently wrapped in electrical tape. 6/11/2025
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.5 Wedge Rope Sockets 2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced. 6/11/2025
A17.1-2016 : Elevators 2.27 - Rope fastenings 2.20.9 x Hoist rope tail retaining clips shall be properly spaced.
A17.1-2019: Elevators 1.6 - Car emergency signal 2.27.1.1.1 x The video function of the emergency communications system is not working properly. Take corrective action and re-test. Customer to also apply for a variance from the State of Missouri for the video function of the emergency communication system. 12/8/2025