Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/4/2025
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space No No Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. 12/4/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 Yes No Front door open button is not functioning on Phase 2 fire service.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing not complete: The following items still need to be tested/inspected: car door switch and restrictor, governor, safeties, unintended movement, emergency power and door closing force.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Acceptance testing is incomplete. The following items still need to be tested and recorded: Slide, pull out/pull thru, governor electrical & mechanical speeds, door closing pressure, ring & string, fire alarm initiating device testing, emergency power. 5/3/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 Yes No ARU/Battery pack switch missing in disconnect. 5/3/2023
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Yes No Install all missing covers in machine room. 5/3/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Yes No Main and lighting disconnect shall be labeled. 5/3/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device Yes Yes The following fire service devices failed to recall elevator. Machine room smoke, top of hoistway smoke, and all heat detectors (not tested). 5/3/2023
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No 2.3.3 - Top of machine space (hoistway) lighting and outlet shall work. 5/3/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Yes No Pit light switch is not accessible from landing due to obstructions and location. 5/3/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device Yes Yes Top of hoistway smoke needs to be reprogrammed. 5/4/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device Yes Yes All heat detectors shall be tested. 5/4/2023